powerPerfector supply a range of models for all organisations; public and private, large and small.
|
Rating kVA |
Height |
Width |
Depth |
Weight approx |
|
pP30kVA / 45A |
540 |
440 |
450 |
100 |
|
pP50kVA / 70A |
540 |
440 |
450 |
130 |
|
pP70kVA / 100A |
540 |
440 |
450 |
150 |
|
pP105kVA / 150A |
780 |
580 |
550 |
180 |
|
pP150kVA / 220A |
780 |
580 |
550 |
220 |
|
pP210kVA / 300A |
810 |
570 |
670 |
250 |
|
pP280kVA / 400A |
860 |
580 |
660 |
280 |
|
pP350kVA / 500A |
1100 |
600 |
700 |
300 |
|
pP420kVA / 600A |
1100 |
600 |
700 |
400 |
|
pP560kVA / 800A |
1200 |
670 |
720 |
480 |
|
pP740kVA / 1050A |
1400 |
820 |
830 |
600 |
|
pP830kVA / 1200A |
1600 |
1000 |
900 |
630 |
|
pP1000kVA / 1450A |
1600 |
1000 |
900 |
750 |
|
pP1250kVA / 1800A |
1600 |
1050 |
1000 |
850 |
|
pP1500kVA / 2150A |
1600 |
1050 |
1000 |
950 |
|
pP2000kVA / 2900A |
2100 |
1200 |
1900 |
1250 |
N.B. We are able to provide Optimisation settings from 1% to 12%, and unit sizes up to 3500kVA.
Specifications of the powerPerfector:
|
Product |
intensive voltage power optimiser |
|
Phases |
three phase (3 & 4 wire type) |
|
Frequency |
50/60 Hz |
|
Primary voltage |
400V |
|
Secondary voltage |
400V - 6%, 7%, 8%, 9% down |
|
Voltage regulation |
less than 0.5% |
|
Insulation class |
H (180°C) |
The powerPerfector Plus features dynamic voltage power optimisation, in addition to the power quality improvements afforded by the standard powerPerfector. Suitable for electrical supplies with high volatility, the powerPerfector Plus will adapt to changing voltage conditions to give an optimised output in a fixed band. Output voltage can be adjusted online and on-load through the unit's user interface, which can easily interface with a BMS or other control system. This makes the powerPerfector Plus ideal for sites with critical equipment, or those which suffer from an unstable supply.
The powerPerfector device is CE marked, and complies with BS EN 60076-11:2004. NaREC (UK) have recently undertaken power quality and electrical type testing. The technology has also completed Japanese (CB) and NATA (Australian and S.E. Asian) accreditation, and has been ASTA tested by a UKAS laboratory. All installations are carried out by NIC EIC registered engineers to BS 7671 17th Edition.